Dây nhiệt

Thông tin chi tiết

– Twin-conductor switching heat sensing cable
–  Effective monitoring at precise point of risk
–  Economical, reliable and durable detection
–  Simple and easy to install
–  Applied where other types of fire detection are unsuitable
Operation
–  Alarmline Digital cable operates by short-circuiting in a fire condition or where acceptable operating
temperature levels are exceeded, to provide a quick, positive and reliable signal.
–  Alarmline Digital may be used as a stand-alone detection facility with a sensor open circuit FAULT or short
circuit FIRE condition, monitored by an associated simple electrical device.
–  As an integral part of a fire protection system, Alarmline Digital cable may be used as a conventional detector and
operate automatic extinguishing systems via an Extinguishing Control
Panel (ECP). See KIDDE FIRE
–  PROTECTION datasheet E9832-327
–  As a cable and detector in one, installed close to potential sources of fire, Alarmline Digital cable provides
economical detection for a wide range of risks which include:
–  Rack storage
–  Vehicle engine bays
–  Floating roof fuel storage tanks
–  Turbines
–  Boiler fronts
–  Ships’ holds
–  Rail locomotives and rolling stock.
–  All these risks fall well within.
–  Alarmline Digital cable’s continuous operating ambient limits of -65°C to +200°C.
Installation
–  Ease of handling and stripping of the cable permits quick installation and allows conventional or proprietary
methods of support to be employed.Nail type cable clips should not be used. Care must be taken to avoid
mechanical impact, kinking, unacceptable heat sources or other factors which may affect the integrity of the cable.


Đánh giá

Chưa có đánh giá nào.

Hãy là người đầu tiên nhận xét “Dây nhiệt”

Khi có nhu cầu về PCCC xin vui lòng liên hệ:
CÔNG TY CỔ PHẦN TM-XD PCCC QUỐC AN
Đ/c: Quoc An Building 231/18 Nguyễn Phúc Chu, P.15, Q. Tân Bình, TP. HCM
Hotline: 0907080979 - 028.2247.1234
Email: quocan@quocanpccc.com
Website: quocanpccc.com / thietbipccc24h.com