Module cách ly sự cố
Thông số kĩ thuật
Isolation Module A6C50000005
The isolation module is used to isolate a short circuit on the detection
bus. The device will automatically recover to its normal status when the
cause of the short circuit disapears.
• The isolation module separates a short circuit on the F-Bus.
• Parallel connection on the first place of each branch or stub is possible.
• No device address is required.
• When a single loop is used to connect devices mounted on several
floors it is recommended to install one isolation module on each floor.
• Up to 25 load factors can be mounted to an isolation module.
• The connection is polarity free.
• Faults will be automatically detected and displayed on the controller.
Operating temperature -20… +50 °C
Relative humidity ≤95 % (40 ± 2 °C)
Activation current ≤0.5 mA
Pass through voltage ≤1 VDC
Wiring Capacity 1.0… 1.5 mm²
Data sheet A5Q00016395A